Sanyu Sjr3-2000 Series External Contactor Type Soft Starter

Certification: ISO9001, CCC
Protection: Shock Resistance
Installation: Hanging
Housing: UPR
Transport Package: Carton
Specification: 130*160*197mm
Samples:
US$ 150/Piece 1 Piece(Min.Order)
| Request Sample
Customization:
Diamond Member Since 2012

Suppliers with verified business licenses

Rating: 5.0/5
Manufacturer/Factory, Trading Company

Basic Info.

Model NO.
SJR3-2000
Trademark
Sanyu
Origin
Shanghai
Production Capacity
10000 Per Month

Product Description

Sanyu Sjr3-2000 Series External Contactor Type Soft Starter

Sanyu Sjr3-2000 Series External Contactor Type Soft Starter
Basic functions
Code setting function
Sanyu Sjr3-2000 Series External Contactor Type Soft Starter


Protection Functions

Description of protection functions

SJR3 series soft starter possesses complete protection functions to protect the operation security of the soft starter and the motor. During operation, the protection level and protection parameters should be properly set based on different circumstances.
1.Over-heating protection of the soft starter: the protection will start when the temperature rises to 80ºC±5ºC , and  it will stop when the temperature falls to 55ºC(lowest).
2.Delayed time of input phase loss protection: <3s.
3.Delayed time of output phase loss protection: <3s.
4.Delayed time of input three-phase unbalance proicciion: <3s. Taking the deviation of current in each phase is over 50%±10% as the criteria, when the load current is less than 30% of the nominal rated value of the  soft starter, it is confirmed that the deviation will increase.
5.Protection time of over-current during starting: the protection time shall be continued to be longer than 5 times of the maximum operating current of code F5.
6.Protection time of overloading in running: inverse time limit thermal protection shall be provided based on the maximum operating current of code F6, see the tripping protection time curve.
7.Delayed time for power under-voltage protection: when the power voltage is under the extreme value 40%, the protection time< 0.5s, when the power voltage is below the set value, the protection time< 3s.
8.Delayed time for power overvoltage protection: when the power voltage is over the extreme value 130%, the protection time< 0.5s, when the power voltage is over the set value, the protection time< 3s.
9.Delayed lime for load short circuit protection < 0.1s, if the current is more than 10 times of the nominal rated value of the soft starter, this protection shall not replace the fuse or short circuit protection device.

The above time parameters are the periods from the valid signal being delected to the tripping protection directive being given; these parameters are for informaiion only. In the event that the protection functions of the soft starter fails to meet the requiremems of customers, special protection devices should be installed to ensure the safety.

Protection tripping voltage curve

Motor thermal protection tripping time curve based on IEC60947-4-2 standard is shown as follows:

Sanyu Sjr3-2000 Series External Contactor Type Soft Starter

Warranty and after-sale service
Sanyu Sjr3-2000 Series External Contactor Type Soft Starter
Sanyu Sjr3-2000 Series External Contactor Type Soft Starter
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Diamond Member Since 2012

Suppliers with verified business licenses

Rating: 5.0/5
Manufacturer/Factory, Trading Company
Management System Certification
ISO 9001, QC 080000
Export Year
2007-03-01