| Customization: | Available |
|---|---|
| Application: | High-performance Transducer, High Frequency Converter Transducer |
| Output Type: | Triple |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
| Item | description | |
| input |
Rated voltage, frequency | Single phase, 220V, 50Hz/60Hz; 3 phase, 380V, 50Hz/60Hz |
| Allowed fluctuation | Continuous voltage fluctuation: within± 10%, instant voltage fluctuation: within -15%10%; voltage imbalance: < 3%; frequency fluctuation: within 5%. | |
| output | Voltage | Single phase, 220V & 3 phase, 380V |
| Output frequency | 0~600Hz. | |
| Overload capability | 150% rated current, 1 minutes; 180% rated current, 1 seconds | |
| control trait | Command input mode | By LCD keypad, by terminals, by PC through serial communication port. |
| Control mode | Open loop vector control, V/F control. | |
| Speed setting method | By keypad, by analog, by PC through serial communication port | |
| Speed setting precision | Digital command± 0.01%(-10 +40) analog command± 0.1%(25° C± 10) |
|
| Speed setting resolution | Digital command: 0.01Hz; analog command: 0.1% of maximum frequency | |
| Speed control accuracy | Open loop vector control: ± 0.5%; (25° C± 10) | |
| Speed regulation range | Open loop vector control: 1: 100 | |
| Torque control response | Open loop vector control: < 200ms. | |
| Start torque | Open loop vector control: 150% of rated torque at 0.5Hz. | |
| Torque control accuracy | ± 5% | |
| Set reference voltage supply output | 1 port, +10V, 5mA | |
| Control voltage supply output | 24V, 100mA | |
| Analogy input | 2 terninal, No. 4 terminal is use for voltage, No. 5 is used for voltage and current input | |
| Analog meter output | 1 terminal, 0/4~20mA or 0~10V available for it |
|
| DO frequency signal output | 1 port, high-frequency signal output(programmable) | |
| Collector open-loop output | One terminal | |
| Programmable relay output | contactor capacity: 250V AC/3A or 30V DC/1A | |
| Serial communication port | RS-485 connector RS485+, RS485- | |
| 4 bits LED display | setting frequency, output frequency, output voltage, output current, motor speed, output torque, switch value terminal, programming menu parameters and fault code. | |
| Five indication lamp | Parameter unit, RUN/STOP status, special status, charging status. | |
| Protection function | Protection function | Over voltage, under voltage, current limitation, over current, overload of inverter, overload of motor, overheat, overvoltage stallout, load short circuit, phase fault. |
| Protection degree | IP21 | |
| Cooling mode | Forced air cooling | |
| envirenment | Ambient termearture | -10° C, +40° C |
| Termperature | 2090% RH(no condensation) | |
| Storage termperature | -20° C, + 60° C | |
| Application area | indoor(no corrosive odor, dust) | |
| Installation area | Altitude is not more than 1000meter, no dust, no corrosive oder, no direct sunlight. | |
| Vibration | less than5.9m/ S 2 |
|